Short description
Bus controller EtherCAT slave
General information
B&R ID code 0xAC23
Status indicators Module status, bus function
Diagnostics
Module status Yes, using LED status indicator and software
Bus function Yes, using LED status indicator and software
Power consumption
Bus 1.68 W
Additional power dissipation caused by actuators (resistive) [W] -
Certifications
CE Yes
UKCA Yes
ATEX Zone 2, II 3G Ex nA nC IIA T5 Gc
IP20, Ta (see X20 user's manual)
FTZÚ 09 ATEX 0083X
UL cULus E115267
Industrial control equipment
HazLoc cCSAus 244665
Process control equipment
for hazardous locations
Class I, Division 2, Groups ABCD, T5
KC Yes
Interfaces
Fieldbus EtherCAT slave
Variant 2x shielded RJ45
Line length Max. 100 m between 2 stations (segment length)
Transfer rate 100 Mbit/s
Transfer
Physical layer 100BASE-TX
Half-duplex Yes
Full-duplex Yes
Autonegotiation Yes
Auto-MDI/MDIX Yes
Hub propagation delay 750 ns
Min. cycle time
Fieldbus 200 μs
X2X Link 200 μs
Synchronization between bus systems possible Yes
Electrical properties
Electrical isolation EtherCAT isolated from bus and I/O
Operating conditions
Mounting orientation
Horizontal Yes
Vertical Yes
Installation elevation above sea level
0 to 2000 m No limitation
>2000 m Reduction of ambient temperature by 0.5°C per 100 m
Degree of protection per EN 60529 IP20
Ambient conditions
Temperature
Operation
Horizontal mounting orientation 0 to 55°C
Vertical mounting orientation 0 to 50°C
Derating -
Storage -25 to 70°C
Transport -25 to 70°C
Relative humidity
Operation 5 to 95%, non-condensing
Storage 5 to 95%, non-condensing
Transport 5 to 95%, non-condensing
Mechanical properties
Note Order 1x terminal block X20TB12 separately.
Order 1x power supply module X20PS9400 or X20PS9402 separately.
Order 1x bus base X20BB80 separately.
Pitch 37.5+0.2 mm
Numero materiale:
X20BC00G3
Descrizione:
  • Fieldbus: EtherCAT
  • Auto-configuration of I/O modules
  • I/O configuration and firmware update via the fieldbus (FoE)
  • Full support of the modular slice concept via CoE (CANopen over EtherCAT)
  • Configurable I/O cycle (0.2 to 4 ms)
  • Synchronization between the fieldbus and X2X Link

EtherCAT is an Ethernet-based fieldbus developed by Beckhoff. This protocol is suitable for both hard and soft real-time requirements in automation technology. In addition to a ring structure, which becomes logically necessary because of the summation frame telegram used, the EtherCAT technology also physically supports topologies such as line, tree, star (limited) and combinations of these topologies. B&R's X20BC80G3 (expandable bus controller module) and X20HB88G0 (standalone junction base module) are available for implementing these topologies.

EtherCAT slave devices take the data designated for them from a telegram as it is passing through the device. Input data is also added to the telegram as it is passing through. The bus controller allows X2X Link I/O modules to be coupled to EtherCAT and operated on any EtherCAT master system. A transition between IP20 and IP67 protection outside of the control cabinet is possible by arranging X20, X67 or XV modules one after the other as needed at distances up to 100 m.

Master systems without FoE (File access over EtherCAT) support require an appropriate configuration tool to transfer the configuration (optional).

With multifunction modules, the bus controller supports only the default function model in the event of automatic configuration by the bus controller (see the respective module description).

All other function models are supported when configured accordingly in Automation Studio V4.3 or later.

Automation Studio kann kostenlos von der B&R Webseite www.br-automation.com heruntergeladen werden. Die Evaluierungslizenz darf unentgeltlich zur Erstellung vollständiger Konfigurationen der Feldbus Bus Controller benützt werden.

Accessori obbligatori
System modules for bus controllers
X20BB80 X20 bus base, for X20 base module (BC, HB, etc.) and X20 power supply module, X20 end cover plates (left and right) X20AC0SL1/X20AC0SR1 included
X20PS9400 X20 power supply module, for bus controller and internal I/O power supply X2X Link power supply
X20PS9402 X20 power supply module, for bus controller and internal I/O power supply, X2X Link supply, supply not galvanically isolated
Terminal blocks
X20TB12 X20 terminal block, 12-pin, 24 VDC keyed
Aggiornamenti HW di Automation Studio Versione (data) Download
V4.3 HW Upgrade (X20BC00G3) EXE / 774 KB
Certificati Versione (data) Download
244665 CSA HazLoc CoC X20, X67 PDF / 158 KB
E115267 UL CoC X20 PDF / 1 MB
EU Declaration ATEX X20 PDF / 218 KB
EU Declaration of conformity PLC X20 PDF / 169 KB
FTZU 09 ATEX 0083X PDF / 771 KB
UK Declaration PLC X20 PDF / 151 KB
X20, X67 KC certificates PDF / 6 MB
Documentazione Versione (data) Download
Data sheet X20BC00G3 PDF / 197 KB
EtherCAT Bus Controller User's Manual PDF / 2 MB
Installation- / EMC-Guide PDF / 20 MB
X20 Package leaflet ATEX/CSA PDF / 2 MB
X20 System User´s Manual PDF / 7 MB
E-CAD (Electro o EPLAN Template) Versione (data) Download
X20 EPLAN P8 from V2.4 EXE / 160 MB
File di descrizione delle apparecchiature Fieldbus Versione (data) Download
X20BC00G3 ESI File ZIP / 3 KB
M-CAD (Mechan. Template) Versione (data) Download
3D File STEP/DXF X20BC and X20IF Module ZIP / 1 MB

Si prega di scegliere il Paese e la lingua

B&R Logo