Short description
Bus controller | PROFINET IO slave |
General information
B&R ID code | 0xBB7D |
Status indicators | Module status, bus function |
Diagnostics | |
Module status | Yes, using LED status indicator and software |
Bus function | Yes, using LED status indicator and software |
Power consumption | |
Bus | 2.5 W |
Additional power dissipation caused by actuators (resistive) [W] | - |
Certifications | |
CE | Yes |
UKCA | Yes |
ATEX |
Zone 2, II 3G Ex nA nC IIA T5 Gc IP20, Ta (see X20 user's manual) FTZÚ 09 ATEX 0083X |
UL |
cULus E115267 Industrial control equipment |
HazLoc |
cCSAus 244665 Process control equipment for hazardous locations Class I, Division 2, Groups ABCD, T5 |
Interfaces
Electrical properties
Electrical isolation | PROFINET isolated from bus and I/O |
Operating conditions
Mounting orientation | |
Horizontal | Yes |
Vertical | Yes |
Installation elevation above sea level | |
0 to 2000 m | No limitation |
>2000 m | Reduction of ambient temperature by 0.5°C per 100 m |
Degree of protection per EN 60529 | IP20 |
Ambient conditions
Temperature | |
Operation | |
Horizontal mounting orientation | -25 to 60°C |
Vertical mounting orientation | -25 to 50°C |
Derating | - |
Storage | -40 to 85°C |
Transport | -40 to 85°C |
Relative humidity | |
Operation | 5 to 95%, non-condensing |
Storage | 5 to 95%, non-condensing |
Transport | 5 to 95%, non-condensing |
Numero materiale:
X20BC00E3Descrizione:
- Fieldbus: PROFINET IO
- I/O configuration via the fieldbus
- Conformance Class B (RT)
- Minimum cycle time 1 ms
- Integrated switch for cabling multiple slaves
- 100 Mbit/s full duplex mode
- Up to 1440 bytes of input data and up to 1440 bytes of output data are possible
- Integrated website
- PROFINET diagnostics and module diagnostics during runtime from within the master environment
- Module and switch diagnostics during runtime using the website or SNMP
PROFINET (Process Field Network) is an Industrial Ethernet protocol. It uses TCP/IP and is real-time capable.
X20 modules or other modules based on X2X Link can be connected to the bus controller. Modular system configurations are optimally supported by PROFINET. Using the device description file (GSDML format), it is very easy to handle project configuration in the respective engineering tool from the manufacturer of the master device.
Accessori obbligatori
System modules for bus controllers
X20BB80 | X20 bus base, for X20 base module (BC, HB, etc.) and X20 power supply module, X20 end cover plates (left and right) X20AC0SL1/X20AC0SR1 included |
X20PS9400 | X20 power supply module, for bus controller and internal I/O power supply X2X Link power supply |
X20PS9402 | X20 power supply module, for bus controller and internal I/O power supply, X2X Link supply, supply not galvanically isolated |
Terminal blocks
X20TB12 | X20 terminal block, 12-pin, 24 VDC keyed |
Documentazione | Versione (data) | Download |
---|---|---|
Data sheet X20(c)BC00E3 | PDF / 397 KB | |
Installation- / EMC-Guide | PDF / 20 MB | |
PROFINET IO Bus Controller User's Manual | PDF / 5 MB | |
X20 Package leaflet ATEX/CSA | PDF / 2 MB | |
X20 System User´s Manual | PDF / 7 MB |
E-CAD (Electro o EPLAN Template) | Versione (data) | Download |
---|---|---|
X20 EPLAN P8 from V2.4 | EXE / 160 MB |
File di descrizione delle apparecchiature Fieldbus | Versione (data) | Download |
---|---|---|
PROFINET Bus controller GSD Package | ZIP / 1 MB |
M-CAD (Mechan. Template) | Versione (data) | Download |
---|---|---|
3D File STEP/DXF X20BC and X20IF Module | ZIP / 1 MB |