Short description
Bus controller | POWERLINK (V1/V2) controlled node |
General information
B&R ID code | 0x1F1E |
Status indicators | Module status, bus function |
Diagnostics | |
Module status | Yes, using LED status indicator and software |
Bus function | Yes, using LED status indicator and software |
Support | |
Dynamic node allocation (DNA) | Yes |
Power consumption | |
Bus | 2 W |
Additional power dissipation caused by actuators (resistive) [W] | - |
Certifications | |
CE | Yes |
UKCA | Yes |
ATEX |
Zone 2, II 3G Ex nA nC IIA T5 Gc IP20, Ta (see X20 user's manual) FTZÚ 09 ATEX 0083X |
UL |
cULus E115267 Industrial control equipment |
HazLoc |
cCSAus 244665 Process control equipment for hazardous locations Class I, Division 2, Groups ABCD, T5 |
DNV |
Temperature: B (0 to 55°C) Humidity: B (up to 100%) Vibration: B (4 g) EMC: B (bridge and open deck) |
CCS | Yes |
LR | ENV1 |
KR | Yes |
ABS | Yes |
BV |
EC33B Temperature: 5 - 55°C Vibration: 4 g EMC: Bridge and open deck |
KC | Yes |
Interfaces
Electrical properties
Electrical isolation | POWERLINK isolated from bus and I/O |
Operating conditions
Mounting orientation | |
Horizontal | Yes |
Vertical | Yes |
Installation elevation above sea level | |
0 to 2000 m | No limitation |
>2000 m | Reduction of ambient temperature by 0.5°C per 100 m |
Degree of protection per EN 60529 | IP20 |
Ambient conditions
Temperature | |
Operation | |
Horizontal mounting orientation | -25 to 60°C |
Vertical mounting orientation | -25 to 50°C |
Derating | - |
Storage | -40 to 85°C |
Transport | -40 to 85°C |
Relative humidity | |
Operation | 5 to 95%, non-condensing |
Storage | 5 to 95%, non-condensing |
Transport | 5 to 95%, non-condensing |
Numero materiale:
X20BC0083Descrizione:
- POWERLINK
- I/O configuration and firmware update via the fieldbus
- Integrated hub for economical wiring
The bus controller makes it possible to connect X2X Link I/O nodes to POWERLINK. It is also possible to operate the X2X Link cycle synchronously 1:1 or synchronous to POWERLINK using a prescaler.
POWERLINK is a standard protocol for Fast Ethernet equipped with hard real-time characteristics. The POWERLINK Standardization Group (EPSG) ensures that the standard remains open and is continually developed:: www.ethernet-powerlink.org.
Accessori obbligatori
System modules for bus controllers
X20BB80 | X20 bus base, for X20 base module (BC, HB, etc.) and X20 power supply module, X20 end cover plates (left and right) X20AC0SL1/X20AC0SR1 included |
X20PS9400 | X20 power supply module, for bus controller and internal I/O power supply X2X Link power supply |
X20PS9402 | X20 power supply module, for bus controller and internal I/O power supply, X2X Link supply, supply not galvanically isolated |
Terminal blocks
X20TB12 | X20 terminal block, 12-pin, 24 VDC keyed |
Aggiornamenti HW di Automation Studio | Versione (data) | Download |
---|---|---|
V2.6 HW Upgrade (X20BC0083) | EXE / 2 MB | |
V3.0 HW Upgrade (X20BC0083) | EXE / 2 MB | |
V4.0 HW Upgrade (X20BC0083) | EXE / 2 MB |
Documentazione | Versione (data) | Download |
---|---|---|
Data sheet X20(c)BC0083 | PDF / 1 MB | |
Installation- / EMC-Guide | PDF / 20 MB | |
POWERLINK Bus Controller User's Manual | PDF / 2 MB | |
X20 Package leaflet ATEX/CSA | PDF / 2 MB | |
X20 System User´s Manual | PDF / 7 MB |
E-CAD (Electro o EPLAN Template) | Versione (data) | Download |
---|---|---|
X20 EPLAN P8 from V2.4 | EXE / 160 MB |
File di descrizione delle apparecchiature Fieldbus | Versione (data) | Download |
---|---|---|
X20BC0083 XDD Package | ZIP / 13 MB |
M-CAD (Mechan. Template) | Versione (data) | Download |
---|---|---|
3D File STEP/DXF X20BC and X20IF Module | ZIP / 1 MB |